FREE SHIPPING on every walk-in we quote  ·  Same-day quote
Condensing unit guide

Walk-in cooler condensing units

Updated

A walk-in cooler condensing unit is the cabinet that holds the compressor and the condenser, joined by a refrigerant line set to the evaporator inside the box. We supply them from 1/2 HP to 6 HP, for walk-in coolers and walk-in freezers, in R-448A and R-454A. This guide shows which size goes on which walk-in, what each one is rated, and what to check before you buy.

Quick answer

A condensing unit is the part of a walk-in refrigeration system that holds the compressor and the condenser. It sits outdoors or indoors and connects through a line set to the evaporator hanging inside the box.

On our standard packages a walk-in cooler carries 1/2 HP on a 6x6, 3/4 HP on a 6x8 or 8x8, 1 HP on an 8x10 or 10x10 and 1 1/2 HP on a 10x12. A walk-in freezer needs more: 1 HP on a 6x6 and 2 1/2 HP on an 8x10 or 10x10. Across our range, cooler units are rated 6,580 to 50,770 BTU/h at 95°F and freezer units 2,580 to 20,840 BTU/h.

Horsepower comes from the heat load, not the floor area, so glass doors, an outdoor location or a custom size can change the answer. We do the load calculation before anything is quoted.

The parts

What a condensing unit does

Walk-in refrigeration has two halves. The evaporator takes the heat out of the box, and the condensing unit gets rid of it.

  • Condensing unit: one cabinet holding the compressor and the condenser. It sits outdoors on a pad or roof, or indoors.
  • Compressor: inside the condensing unit, it pumps the refrigerant around the system. All 301 of our condensing units use a scroll compressor.
  • Condenser: also inside the condensing unit, it gives off the heat taken out of the box.
  • Evaporator (unit cooler): hung from the ceiling inside the box, it takes the heat out of the air.
  • Line set: the copper refrigerant lines that join the condensing unit and the evaporator. A refrigeration contractor runs, evacuates and charges them on site.
  • Self-contained system: both halves in one unit, close to plug-and-play, including drop-in models that mount through a factory ceiling cutout.

A compressor is not a separate purchase here: it comes inside a complete, brand new condensing unit, matched to an evaporator for your box. The condensing units are UL and cUL listed.

Sizing

Which size fits your walk-in

Start from the standard package for your footprint. The heat load then confirms it or changes it.

Refrigeration horsepower on our standard walk-in packages
Nominal sizeWalk-in cooler (35°F)Walk-in freezer (-10°F)
6x61/2 HP: R-448A or R-454A1 HP: R-448A or R-454A
6x83/4 HP: R-448A or R-454A1 1/2 HP: R-448A or R-454A
8x83/4 HP: R-448A or R-454AConfirmed at quote
8x101 HP: R-448A or R-454A2 1/2 HP: R-448A or R-454A
10x101 HP: R-448A or R-454A2 1/2 HP: R-448A or R-454A
10x121 1/2 HP: R-448A or R-454ASized at quote

Coolers on this table hold 35°F. Freezers are specified at -10°F with the insulated floor included. Sizes are nominal, and our walk-in cooler size guide shows what each footprint holds.

  • Glass doors can call for more refrigeration on the same footprint.
  • An outdoor location can change the system too.
  • A custom size is sized from its own heat load, up to 6 HP in this range.
  • Warm product. If you need to bring a product down to a certain temperature in a certain time, tell us, because the refrigeration is sized to it.
Capacity

BTU ratings, 1/2 to 6 HP

Published capacity of every size at 95°F outdoor air, in both refrigerants. Each link opens that unit’s models and matched evaporators.

Walk-in cooler condensing units

Walk-in cooler condensing units, capacity at 95°F outdoor air
SizeR-448A, rated at 95°FR-454A, rated at 95°FCabinet weight
1/2 HP1/2 HP R-448A cooler unit
6,580 BTU/h
1/2 HP R-454A cooler unit
7,120 BTU/h
195 lb
3/4 HP3/4 HP R-448A cooler unit
8,020 BTU/h
3/4 HP R-454A cooler unit
8,370 BTU/h
195 lb
1 HP1 HP R-448A cooler unit
9,380 to 9,680 BTU/h
1 HP R-454A cooler unit
9,350 to 10,230 BTU/h
195 lb
1 1/4 HP1 1/4 HP R-448A cooler unit
12,140 BTU/h
1 1/4 HP R-454A cooler unit
12,660 BTU/h
205 lb
1 1/2 HP1 1/2 HP R-448A cooler unit
13,690 BTU/h
1 1/2 HP R-454A cooler unit
13,970 BTU/h
210 lb
2 HP2 HP R-448A cooler unit
16,840 BTU/h
2 HP R-454A cooler unit
16,890 BTU/h
215 lb
2 1/2 HP2 1/2 HP R-448A cooler unit
18,770 BTU/h
2 1/2 HP R-454A cooler unit
18,490 BTU/h
230 lb
2 3/4 HP2 3/4 HP R-448A cooler unit
24,100 BTU/h
2 3/4 HP R-454A cooler unit
24,880 BTU/h
305 lb
3 HP3 HP R-448A cooler unit
27,960 BTU/h
3 HP R-454A cooler unit
27,380 BTU/h
305 lb
3 1/2 HP3 1/2 HP R-448A cooler unit
29,760 BTU/h
3 1/2 HP R-454A cooler unit
30,160 BTU/h
325 lb
4 HP4 HP R-448A cooler unit
32,160 to 35,030 BTU/h
4 HP R-454A cooler unit
32,590 to 33,420 BTU/h
352 to 700 lb
4 1/2 HP4 1/2 HP R-448A cooler unit
39,190 BTU/h
4 1/2 HP R-454A cooler unit
37,170 BTU/h
375 lb
5 HP5 HP R-448A cooler unit
35,180 to 43,160 BTU/h
5 HP R-454A cooler unit
36,490 to 43,410 BTU/h
383 to 710 lb
6 HP6 HP R-448A cooler unit
35,080 to 47,250 BTU/h
6 HP R-454A cooler unit
42,680 to 50,770 BTU/h
405 to 710 lb

Walk-in freezer condensing units

Walk-in freezer condensing units, capacity at 95°F outdoor air
SizeR-448A, rated at 95°FR-454A, rated at 95°FCabinet weight
1 HP1 HP R-448A freezer unit
2,580 BTU/h
1 HP R-454A freezer unit
2,850 BTU/h
195 lb
1 1/3 HP1 1/3 HP R-448A freezer unit
3,380 BTU/h
1 1/3 HP R-454A freezer unit
3,820 BTU/h
195 lb
1 1/2 HP1 1/2 HP R-448A freezer unit
4,030 BTU/h
1 1/2 HP R-454A freezer unit
4,470 BTU/h
195 lb
2 1/3 HP2 1/3 HP R-448A freezer unit
6,370 BTU/h
2 1/3 HP R-454A freezer unit
6,970 BTU/h
230 lb
2 1/2 HP2 1/2 HP R-448A freezer unit
7,980 BTU/h
2 1/2 HP R-454A freezer unit
8,450 BTU/h
240 lb
3 HP3 HP R-448A freezer unit
9,000 BTU/h
3 HP R-454A freezer unit
9,390 BTU/h
245 lb
3 1/2 HP3 1/2 HP R-448A freezer unit
11,140 BTU/h
3 1/2 HP R-454A freezer unit
11,430 BTU/h
255 lb
4 HP4 HP R-448A freezer unit
12,990 BTU/h
4 HP R-454A freezer unit
14,500 BTU/h
352 lb
5 HP5 HP R-448A freezer unit
16,070 BTU/h
5 HP R-454A freezer unit
17,770 BTU/h
367 lb
6 HP6 HP R-448A freezer unit
19,440 BTU/h
6 HP R-454A freezer unit
20,840 BTU/h
383 lb

A range means the size comes in models with different ratings. Compare BTU, not horsepower alone. A 1 HP freezer unit is rated 2,580 to 2,850 BTU/h where a 1 HP cooler unit is rated 9,350 to 10,230 BTU/h, because it works at a far colder temperature. Horsepower does not always rise with capacity either: one 6 HP R-448A cooler model is rated 35,080 BTU/h, below the 39,190 BTU/h of the 4 1/2 HP R-448A cooler unit, because these sizes come in more than one series.

Every model number, voltage and cabinet size is on its own page, and all of them are listed on our walk-in refrigeration units page.

Power

Voltage and phase

Check the service at your site first. It can decide which model you can use.

  • 208-230 V single phase: available on every size through 5 HP, cooler and freezer, in both refrigerants.
  • 208-230 V three phase: available on every size. At 6 HP, every model is three phase.
  • 460 V three phase, R-454A: cooler units from 1 HP up and freezer units from 2 1/3 HP up.
  • 460 V three phase, R-448A: cooler units at 4, 5 and 6 HP. The R-448A freezer units do not come in 460 V.

Tell us the electrical service at the site when you ask for a quote, so the unit is chosen for the power you have. A licensed electrician makes the connection.

Placement

Where the unit can sit

The location changes the model you need and where the heat ends up.

  • Models for each location. Of our 301 condensing units, 126 are listed for indoor or outdoor use and 175 are for outdoor siting only. Every size comes both ways.
  • Heat goes where the unit is. Every condensing unit gives off heat. A remote indoor unit puts that heat into your building, and a remote outdoor unit sends it outside. In a hot kitchen, an indoor box with an outdoor condensing unit is often the better pairing.
  • Weight. Cabinets run from 195 lb to 710 lb, so plan how the unit gets onto its pad or roof. The table above gives the weight for each size.
  • Distance and air. A remote unit can sit in several places, depending on the length of the line set and the airflow around the cabinet. Our indoor vs outdoor walk-in cooler guide covers what changes outside.
R-448A or R-454A

Choosing the refrigerant

Both refrigerants are current, and every size on this page comes in both.

R-448A and R-454A condensing units
R-448AR-454A
What it isThe non-flammable A1 blend that directly replaces R-404AThe A2L, lower-GWP refrigerant now shipping on new equipment
HandlingStandard A1 practiceMildly flammable, installed to the A2L requirements in the manufacturer’s instructions
Condensing units we list108193

R-404A is being phased down under the AIM Act, so we do not supply it on a new system. R-448A or R-454A replaces it.

Existing walk-ins

Buying a unit for an existing walk-in

You can buy the refrigeration without the box. This is what we need, and what stays with your contractor.

  1. Choose Refrigeration only on the quote form.
  2. Give us the box. Its inside dimensions, the temperature it holds and what goes in it.
  3. Give us the site. Where the condensing unit can sit and the electrical service available.
  4. We size both halves. The condensing unit and the evaporator are sized together from the heat load.
  • Copper and refrigerant. On a remote system, our quote covers the equipment for a complete assembly except the copper tubing and the refrigerant (Freon), which your installer or refrigeration contractor normally supplies.
  • Installation. We supply the equipment and do not install it. A refrigeration contractor sets and connects the unit. The walk-in cooler installation guide shows who does what.
  • Warranty. Refrigeration we quote carries a 1 year compressor warranty, no labor.
Straight answers

Frequently asked

What is a condensing unit on a walk-in cooler?

It is the cabinet that holds the compressor and the condenser. It sits outdoors on a pad or roof, or indoors, and connects through a line set to the evaporator that hangs inside the box.

Is a condensing unit the same as a compressor?

No. The compressor is one part inside the condensing unit, which also holds the condenser. We supply the compressor as part of a complete, brand new condensing unit, and every one of our units uses a scroll compressor.

What size condensing unit does a 10x10 walk-in cooler need?

Our standard 10x10 walk-in cooler carries 1 HP and is specified to hold 35°F. Glass doors, an outdoor location or a different height can change that, so we calculate the heat load before we quote.

What size condensing unit does an 8x10 walk-in freezer need?

Our standard 8x10 walk-in freezer carries 2 1/2 HP, the same as the standard 10x10 freezer, and is specified at -10°F with the insulated floor included.

How many BTU is a 1 HP walk-in cooler condensing unit?

Our 1 HP cooler units are rated 9,350 to 10,230 BTU/h at 95°F, depending on the model and refrigerant. A 1 HP freezer unit is rated 2,580 to 2,850 BTU/h, because it works at a far colder temperature.

Do you sell condensing units on their own?

Yes, for an existing walk-in. Choose Refrigeration only on the quote form and we size the condensing unit and the evaporator together from the heat load.

Are the copper lines and refrigerant included?

No. On a remote system, our quote covers the equipment for a complete assembly except the copper tubing and the refrigerant (Freon), which your installer or refrigeration contractor normally supplies. The contractor also runs, evacuates and charges the line set.

What evaporator goes with a condensing unit?

One sized with it from the heat load. Each unit’s page lists the matched evaporators, including low profile, medium profile and center mount coils. Standard cooler packages use air defrost and freezers use electric defrost. The condensing unit and the evaporator are rated under different conditions, so their BTU figures do not have to be equal.

Can a condensing unit go outdoors?

Yes. Every size comes in models for outdoor siting, and 126 of our 301 units are listed for indoor or outdoor use. See the indoor vs outdoor walk-in cooler guide.

Do walk-in condensing units come in single phase?

Yes, in 208-230 V through 5 HP. Every 6 HP model is three phase, and some sizes also come in 460 V three phase.

Do you install condensing units?

No. We supply the equipment, and a refrigeration contractor sets and connects it. Refrigeration we quote carries a 1 year compressor warranty, no labor.

Get the right unit quoted

Send the size of your walk-in, the temperature it holds, where the unit can sit and your electrical service, or text photos to 954-237-6753. We work out the heat load and reply, usually the same day.

Call Now Get a Free Quote