FREE SHIPPING on every walk-in we quote  ·  Same-day quote
R-454A · Medium Temperature (Cooler)

1-1/4 HP R-454A walk-in cooler refrigeration system

Updated

1 1/4 HP is not a standard cooler package size (those run from 1/2 HP on a 6x6 to 1 1/2 HP on a 10x12). We choose it at quote when the heat load calls for about 12,700 BTU/h at 95°F: a custom size, glass doors or an outdoor location. This class has 8 current R-454A condensing units at 1-1/4 HP, rated 12,660 BTU/h at 95°F ambient, with the 16 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.

Outdoor remote refrigeration condensing unit of the type supplied with a 1-1/4 HP walk-in cooler system
1-1/4
Horsepower
12,660
BTU/h at 95°F ambient
8
Condensing units
16
Matched evaporators
8 models

1-1/4 HP R-454A condensing units

R-454A is an A2L refrigerant: lower GWP, mildly flammable, installed to the manufacturer’s A2L requirements. Compare R-448A and R-454A.

1-1/4 HP R-454A Medium Temperature (Cooler) condensing units, 8 models
ModelSeriesSiting CompressorBTU/h @ 90°F BTU/h @ 95°FElectrical D × W × HWeight
WBON150E4ADA Next-Gen Mini-Con Indoor / Outdoor Scroll · Non-Flooded 13,200 12,660 208-230/1/60 · 1-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WBON150E4AEA Next-Gen Mini-Con Indoor / Outdoor Scroll · Non-Flooded 13,200 12,660 208-230/3/60 · 3-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WBON150E4AGA Next-Gen Mini-Con Indoor / Outdoor Scroll · Non-Flooded 13,200 12,660 460/3/60 · 3-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WFON150E4ADA Next-Gen Mini-Con Outdoor Scroll · Flooded 13,200 12,660 208-230/1/60 · 1-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WFON150E4ADANT Next-Gen Mini-Con Outdoor Scroll · Flooded 13,200 12,660 208-230/1/60 · 1-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WFON150E4AEA Next-Gen Mini-Con Outdoor Scroll · Flooded 13,200 12,660 208-230/3/60 · 3-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WFON150E4AEANT Next-Gen Mini-Con Outdoor Scroll · Flooded 13,200 12,660 208-230/3/60 · 3-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb
WFON150E4AGA Next-Gen Mini-Con Outdoor Scroll · Flooded 13,200 12,660 460/3/60 · 3-ph 28-1/4 × 39-7/8 × 18-3/4″ 205 lb

Manufacturer ratings at 25°F suction.

Choosing the model

Which 1 1/4 HP R-454A model fits your site

1 1/4 HP R-454A is rated up to 12,660 BTU/h at 95°F (about 1.1 tons) at 25°F suction, from 8 Next-Gen Mini-Con models. Compared with the 1 HP below it: 2,430 BTU/h more (24%), a different cabinet, 205 lb against 195 lb. Of its 16 matched unit coolers, 8 also serve the 1 HP. The 1 1/2 HP above it is rated 13,970 BTU/h: the same cabinet, 210 lb against 205 lb here.

  • Next-Gen Mini-Con, 8 models: cabinet 28 1/4 × 39 7/8 × 18 3/4 in., 205 lb; 13,200 BTU/h at 90°F and 12,660 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
  • Indoors or outdoors. WBON150E4ADA on 208-230 V single phase; WBON150E4AEA on 208-230 V three phase; WBON150E4AGA on 460 V three phase.
  • Outdoors only. WFON150E4ADA and WFON150E4ADANT on 208-230 V single phase; WFON150E4AEA and WFON150E4AEANT on 208-230 V three phase; WFON150E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
  • Other refrigerant. The same 1 1/4 HP in R-448A (4 models, Preassembled Remote) is rated 12,140 BTU/h at 95°F, 4% less at the top of the range than R-454A, and weighs 205 lb. See the 1-1/4 HP R-448A walk-in cooler system.
16 unit coolers

Evaporators used with this system

A 1-1/4 HP R-454A condensing unit is matched to 16 medium-temperature unit coolers: 8 center mount and 8 low profile, rated 10,300 to 17,300 BTU/h.

Center mount, air defrost: 8 models
Model and voltageBTU/hCFMFansL × W × H
WAE6A103ADA 115/1/60
WAE6A103DDA 208-230/1/60
10,300 1,144 2 56 × 28-3/8 × 11-1/4″
WAE6A128ADA 115/1/60
WAE6A128DDA 208-230/1/60
12,800 1,806 3 76 × 28-3/8 × 11-1/4″
WAE6A157ADA 115/1/60
WAE6A157DDA 208-230/1/60
15,700 1,716 3 76 × 28-3/8 × 11-1/4″
WAE6A173ADA 115/1/60
WAE6A173DDA 208-230/1/60
17,300 2,408 4 96 × 28-3/8 × 11-1/4″
Low profile, air defrost: 8 models
Model and voltageBTU/hCFMFansL × W × H
WAL6A113ADA 115/1/60
WAL6A113DDA 208-230/1/60
11,300 1,570 2 43-5/8 × 15-1/2 × 18-1/8″
WAL6A141ADA 115/1/60
WAL6A141DDA 208-230/1/60
14,100 1,550 2 43-5/8 × 15-1/2 × 18-1/8″
WAL6A159ADA 115/1/60
WAL6A159DDA 208-230/1/60
15,900 1,550 2 43-5/8 × 15-1/2 × 18-1/8″
WAL6A170ADA 115/1/60
WAL6A170DDA 208-230/1/60
17,000 2,355 3 60-1/8 × 15-1/2 × 18-1/8″

Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.

Straight answers

1-1/4 HP R-454A cooler system questions

How many BTU is a 1 1/4 HP R-454A walk-in cooler system?

The 8 R-454A condensing units in this class are rated 13,200 BTU/h at 90°F ambient and 12,660 BTU/h at 95°F, about 1.1 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-448A the same horsepower is rated 12,140 BTU/h.

What size walk-in cooler does a 1 1/4 HP system fit?

1 1/4 HP is not a standard cooler package size (those run from 1/2 HP on a 6x6 to 1 1/2 HP on a 10x12). We choose it at quote when the heat load calls for about 12,700 BTU/h at 95°F: a custom size, glass doors or an outdoor location. We do the heat load calculation before anything is quoted.

Which 1 1/4 HP R-454A condensing unit goes indoors, and which outdoors?

Indoors or outdoors: WBON150E4ADA on 208-230 V single phase; WBON150E4AEA on 208-230 V three phase; WBON150E4AGA on 460 V three phase. Outdoors only: WFON150E4ADA and WFON150E4ADANT on 208-230 V single phase; WFON150E4AEA and WFON150E4AEANT on 208-230 V three phase; WFON150E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.

Is the 1 1/4 HP R-454A unit single phase, three phase or 460 V?

208-230 V single phase: WBON150E4ADA, WFON150E4ADA and WFON150E4ADANT. 208-230 V three phase: WBON150E4AEA, WFON150E4AEA and WFON150E4AEANT. 460 V three phase: WBON150E4AGA and WFON150E4AGA.

How big and heavy is a 1 1/4 HP R-454A condensing unit?

Next-Gen Mini-Con, 8 models: cabinet 28 1/4 × 39 7/8 × 18 3/4 in., 205 lb; 13,200 BTU/h at 90°F and 12,660 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.

Is 1 1/4 HP on a standard walk-in cooler package?

No. Our standard coolers use 1 HP on an 8x10 or 10x10 and 1 1/2 HP on a 10x12. The 1 1/4 HP, rated 12,660 BTU/h at 95°F, is picked at quote for a load that falls between them.

How does 1 1/4 HP R-454A compare with R-448A?

It is rated 520 BTU/h higher at 95°F, 12,660 against 12,140, about 4%, in a cabinet of the same size at the same 205 lb. R-454A comes in eight models against four and adds 460 V three phase.

Need a 1 1/4 HP R-454A system sized for your walk-in cooler?

Send the inside dimensions and what it will store, tell us where the 1 1/4 HP unit will sit and what power the site has, and you get a drawing and a price.

Get a free quote All refrigeration units

Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.

← 1 HP R-454A freezer  ·  1-1/3 HP R-454A freezer →

Call Now Get a Free Quote