1 HP R-454A walk-in cooler refrigeration system
Updated
A 1 HP system is the standard refrigeration on our 8x10 and 10x10 walk-in cooler packages (7′6″ high, held at 35°F). This class has 13 current R-454A condensing units at 1 HP, rated 9,350 to 10,230 BTU/h at 95°F ambient, with the 14 unit coolers matched to that capacity.
- Capacity. 9,840 to 10,730 BTU/h at 90°F ambient and 9,350 to 10,230 BTU/h at 95°F, about 0.8 to 0.9 tons of refrigeration.
- Next sizes. Smaller: 3/4 HP R-454A walk-in cooler system (8,370 BTU/h). Larger: 1-1/4 HP R-454A walk-in cooler system (12,660 BTU/h).
- Same horsepower in R-448A. 1 HP R-448A walk-in cooler system, 8 condensing units, 9,380 to 9,680 BTU/h at 95°F ambient.
1 HP R-454A condensing units
R-454A is an A2L refrigerant: lower GWP, mildly flammable, installed to the manufacturer’s A2L requirements. Compare R-448A and R-454A.
| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
|---|---|---|---|---|---|---|---|---|
| WBON100M4ADA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 9,840 | 9,350 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WBON100M4AEA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 9,840 | 9,350 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WBON130E4ADA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 10,730 | 10,230 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WBON130E4AEA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 10,730 | 10,230 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON100M4ADA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 9,840 | 9,350 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON100M4ADANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 9,840 | 9,350 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON100M4AEA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 9,840 | 9,350 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON100M4AEANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 9,840 | 9,350 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON130E4ADA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 10,730 | 10,230 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON130E4ADANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 10,730 | 10,230 | 208-230/1/60 · 1-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON130E4AEA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 10,730 | 10,230 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON130E4AEANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 10,730 | 10,230 | 208-230/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
| WFON130E4AGA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 10,730 | 10,230 | 460/3/60 · 3-ph | 28-1/4 × 27-7/8 × 18-3/4″ | 195 lb |
Manufacturer ratings at 25°F suction.
Which 1 HP R-454A model fits your site
1 HP R-454A is rated up to 10,230 BTU/h at 95°F (about 0.9 tons) at 25°F suction, from 13 Next-Gen Mini-Con models. Compared with the 3/4 HP below it: 1,860 BTU/h more (22%), the same cabinet and weight. It adds 460 V three phase, which the 3/4 HP does not offer. Of its 14 matched unit coolers, 10 also serve the 3/4 HP. The 1 1/4 HP above it is rated 12,660 BTU/h: a different cabinet, 205 lb against 195 lb here.
- Next-Gen Mini-Con, 13 models: cabinet 28 1/4 × 27 7/8 × 18 3/4 in., 195 lb; 9,840 to 10,730 BTU/h at 90°F and 9,350 to 10,230 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
- Indoors or outdoors. WBON100M4ADA and WBON130E4ADA on 208-230 V single phase; WBON100M4AEA and WBON130E4AEA on 208-230 V three phase.
- Outdoors only. WFON100M4ADA, WFON100M4ADANT, WFON130E4ADA and WFON130E4ADANT on 208-230 V single phase; WFON100M4AEA, WFON100M4AEANT, WFON130E4AEA and WFON130E4AEANT on 208-230 V three phase; WFON130E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
- Other refrigerant. The same 1 HP in R-448A (8 models, Preassembled Remote) is rated 9,380 to 9,680 BTU/h at 95°F, 5% less at the top of the range than R-454A, and weighs 195 lb. See the 1 HP R-448A walk-in cooler system.
Evaporators used with this system
A 1 HP R-454A condensing unit is matched to 14 medium-temperature unit coolers: 8 low profile and 6 center mount, rated 8,100 to 14,100 BTU/h.
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAE6A085ADA 115/1/60 WAE6A085DDA 208-230/1/60 |
8,500 | 1,204 | 2 | 56 × 28-3/8 × 11-1/4″ |
| WAE6A103ADA 115/1/60 WAE6A103DDA 208-230/1/60 |
10,300 | 1,144 | 2 | 56 × 28-3/8 × 11-1/4″ |
| WAE6A128ADA 115/1/60 WAE6A128DDA 208-230/1/60 |
12,800 | 1,806 | 3 | 76 × 28-3/8 × 11-1/4″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAL6A081ADA 115/1/60 WAL6A081DDA 208-230/1/60 |
8,100 | 775 | 1 | 27-1/8 × 15-1/2 × 18-1/8″ |
| WAL6A088ADA 115/1/60 WAL6A088DDA 208-230/1/60 |
8,800 | 1,600 | 2 | 43-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A113ADA 115/1/60 WAL6A113DDA 208-230/1/60 |
11,300 | 1,570 | 2 | 43-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A141ADA 115/1/60 WAL6A141DDA 208-230/1/60 |
14,100 | 1,550 | 2 | 43-5/8 × 15-1/2 × 18-1/8″ |
Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.
1 HP R-454A cooler system questions
How many BTU is a 1 HP R-454A walk-in cooler system?
The 13 R-454A condensing units in this class are rated 9,840 to 10,730 BTU/h at 90°F ambient and 9,350 to 10,230 BTU/h at 95°F, about 0.8 to 0.9 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-448A the same horsepower is rated 9,380 to 9,680 BTU/h.
What size walk-in cooler does a 1 HP system fit?
A 1 HP system is the standard refrigeration on our 8x10 and 10x10 walk-in cooler packages (7′6″ high, held at 35°F). We do the heat load calculation before anything is quoted.
Which 1 HP R-454A condensing unit goes indoors, and which outdoors?
Indoors or outdoors: WBON100M4ADA and WBON130E4ADA on 208-230 V single phase; WBON100M4AEA and WBON130E4AEA on 208-230 V three phase. Outdoors only: WFON100M4ADA, WFON100M4ADANT, WFON130E4ADA and WFON130E4ADANT on 208-230 V single phase; WFON100M4AEA, WFON100M4AEANT, WFON130E4AEA and WFON130E4AEANT on 208-230 V three phase; WFON130E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
Is the 1 HP R-454A unit single phase, three phase or 460 V?
208-230 V single phase: WBON100M4ADA, WBON130E4ADA, WFON100M4ADA, WFON100M4ADANT, WFON130E4ADA and WFON130E4ADANT. 208-230 V three phase: WBON100M4AEA, WBON130E4AEA, WFON100M4AEA, WFON100M4AEANT, WFON130E4AEA and WFON130E4AEANT. 460 V three phase: WFON130E4AGA.
How big and heavy is a 1 HP R-454A condensing unit?
Next-Gen Mini-Con, 13 models: cabinet 28 1/4 × 27 7/8 × 18 3/4 in., 195 lb; 9,840 to 10,730 BTU/h at 90°F and 9,350 to 10,230 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
Need a 1 HP R-454A system sized for your walk-in cooler?
Send the inside dimensions and what it will store, tell us where the 1 HP unit will sit and what power the site has, and you get a drawing and a price.
Get a free quote All refrigeration units
Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.