4 HP R-454A walk-in cooler refrigeration system
Updated
4 HP is sized at quote for large walk-in coolers, more than twice the horsepower of our standard 10x12 (1 1/2 HP): big custom boxes, glass door walls, coolers outdoors. The heat load calculation sets it; the power on site and the weight the roof or pad can carry then pick the series. This class has 12 current R-454A condensing units at 4 HP, rated 32,590 to 33,420 BTU/h at 95°F ambient, with the 31 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.
- Capacity. 34,010 to 34,940 BTU/h at 90°F ambient and 32,590 to 33,420 BTU/h at 95°F, about 2.7 to 2.8 tons of refrigeration.
- Next sizes. Smaller: 3-1/2 HP R-454A walk-in cooler system (30,160 BTU/h). Larger: 4-1/2 HP R-454A walk-in cooler system (37,170 BTU/h).
- Same horsepower in R-448A. 4 HP R-448A walk-in cooler system, 8 condensing units, 32,160 to 35,030 BTU/h at 95°F ambient.
4 HP R-454A condensing units
R-454A is an A2L refrigerant: lower GWP, mildly flammable, installed to the manufacturer’s A2L requirements. Compare R-448A and R-454A.
| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
|---|---|---|---|---|---|---|---|---|
| WBOS004E4AEA | Next-Gen II | Indoor / Outdoor | Scroll · Non-Flooded | 34,010 | 32,590 | 208/230/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WBOS004E4AGA | Next-Gen II | Indoor / Outdoor | Scroll · Non-Flooded | 34,010 | 32,590 | 460/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WBON400E4ADA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 34,940 | 33,420 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WBON400E4AEA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 34,940 | 33,420 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WBON400E4AGA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 34,940 | 33,420 | 460/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WFOS004E4AEA | Next-Gen II | Outdoor | Scroll · Flooded | 34,010 | 32,590 | 208/230/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WFOS004E4AGA | Next-Gen II | Outdoor | Scroll · Flooded | 34,010 | 32,590 | 460/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WFON400E4ADA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 34,940 | 33,420 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WFON400E4ADANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 34,940 | 33,420 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WFON400E4AEA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 34,940 | 33,420 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WFON400E4AEANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 34,940 | 33,420 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 352 lb |
| WFON400E4AGA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 34,940 | 33,420 | 460/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 352 lb |
Manufacturer ratings at 25°F suction.
Which 4 HP R-454A model fits your site
4 HP R-454A comes in two series rated almost alike, 32,590 and 33,420 BTU/h at 95°F (about 2.7 to 2.8 tons), but built very differently: the Next-Gen Mini-Con weighs 352 lb and runs on every service, single phase included; the Next-Gen II weighs 700 lb and runs on three phase only. Where single phase is all the building has, the Mini-Con is the one.
- Next-Gen II, 4 models: cabinet 49 × 38 5/16 × 36 3/8 in., 700 lb; 34,010 BTU/h at 90°F and 32,590 BTU/h at 95°F; 208-230 V three phase and 460 V three phase.
- Next-Gen Mini-Con, 8 models: cabinet 33 × 43 7/8 × 35 in., 352 lb; 34,940 BTU/h at 90°F and 33,420 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
- Indoors or outdoors. WBON400E4ADA on 208-230 V single phase; WBOS004E4AEA and WBON400E4AEA on 208-230 V three phase; WBOS004E4AGA and WBON400E4AGA on 460 V three phase.
- Outdoors only. WFON400E4ADA and WFON400E4ADANT on 208-230 V single phase; WFOS004E4AEA, WFON400E4AEA and WFON400E4AEANT on 208-230 V three phase; WFOS004E4AGA and WFON400E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
- Other refrigerant. The same 4 HP in R-448A (8 models, Next-Gen II Scroll and Preassembled Remote) is rated 32,160 to 35,030 BTU/h at 95°F, 5% more at the top of the range than R-454A, and weighs 352 to 700 lb. See the 4 HP R-448A walk-in cooler system.
Evaporators used with this system
A 4 HP R-454A condensing unit is matched to 31 medium-temperature unit coolers: 21 medium profile, 8 low profile and 2 center mount, rated 26,800 to 44,800 BTU/h.
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAE6A316ADA 115/1/60 WAE6A316DDA 208-230/1/60 |
31,600 | 3,150 | 5 | 116 × 28-3/8 × 13-3/4″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAL6A289ADA 115/1/60 WAL6A289DDA 208-230/1/60 |
28,900 | 3,140 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A316ADA 115/1/60 WAL6A316DDA 208-230/1/60 |
31,600 | 3,199 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A375ADA 115/1/60 WAL6A375DDA 208-230/1/60 |
37,500 | 3,875 | 5 | 93-1/8 × 15-1/2 × 18-1/8″ |
| WAL6A404ADA 115/1/60 WAL6A404DDA 208-230/1/60 |
40,400 | 4,650 | 6 | 109-5/8 × 15-1/2 × 18-1/8″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAM6A268ADA 115/1/60 WAM6A268DDA 208-230/1/60 WAM6A268FDA 460/1/60 |
26,800 | 2,950 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |
| WAM6A336ADA 115/1/60 WAM6A336DDA 208-230/1/60 WAM6A336FDA 460/1/60 |
33,600 | 6,950 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
| WAM6A448ADA 115/1/60 WAM6A448DDA 208-230/1/60 WAM6A448FDA 460/1/60 |
44,800 | 6,380 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAM6D267DDA 208-230/1/60 WAM6D267EDA 208-230/3/60 WAM6D267FDA 460/1/60 WAM6D267GDA 460/3/60 |
26,800 | 2,950 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |
| WAM6D335DDA 208-230/1/60 WAM6D335EDA 208-230/3/60 WAM6D335FDA 460/1/60 WAM6D335GDA 460/3/60 |
33,600 | 6,950 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
| WAM6D447DDA 208-230/1/60 WAM6D447EDA 208-230/3/60 WAM6D447FDA 460/1/60 WAM6D447GDA 460/3/60 |
44,800 | 6,380 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.
4 HP R-454A cooler system questions
How many BTU is a 4 HP R-454A walk-in cooler system?
The 12 R-454A condensing units in this class are rated 34,010 to 34,940 BTU/h at 90°F ambient and 32,590 to 33,420 BTU/h at 95°F, about 2.7 to 2.8 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-448A the same horsepower is rated 32,160 to 35,030 BTU/h.
What size walk-in cooler does a 4 HP system fit?
4 HP is sized at quote for large walk-in coolers, more than twice the horsepower of our standard 10x12 (1 1/2 HP): big custom boxes, glass door walls, coolers outdoors. The heat load calculation sets it; the power on site and the weight the roof or pad can carry then pick the series.
Which 4 HP R-454A condensing unit goes indoors, and which outdoors?
Indoors or outdoors: WBON400E4ADA on 208-230 V single phase; WBOS004E4AEA and WBON400E4AEA on 208-230 V three phase; WBOS004E4AGA and WBON400E4AGA on 460 V three phase. Outdoors only: WFON400E4ADA and WFON400E4ADANT on 208-230 V single phase; WFOS004E4AEA, WFON400E4AEA and WFON400E4AEANT on 208-230 V three phase; WFOS004E4AGA and WFON400E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
Is the 4 HP R-454A unit single phase, three phase or 460 V?
208-230 V single phase: WBON400E4ADA, WFON400E4ADA and WFON400E4ADANT. 208-230 V three phase: WBOS004E4AEA, WBON400E4AEA, WFOS004E4AEA, WFON400E4AEA and WFON400E4AEANT. 460 V three phase: WBOS004E4AGA, WBON400E4AGA, WFOS004E4AGA and WFON400E4AGA.
How big and heavy is a 4 HP R-454A condensing unit?
Next-Gen II, 4 models: cabinet 49 × 38 5/16 × 36 3/8 in., 700 lb; 34,010 BTU/h at 90°F and 32,590 BTU/h at 95°F; 208-230 V three phase and 460 V three phase. Next-Gen Mini-Con, 8 models: cabinet 33 × 43 7/8 × 35 in., 352 lb; 34,940 BTU/h at 90°F and 33,420 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
Need a 4 HP R-454A system sized for your walk-in cooler?
Send the inside dimensions and what it will store, tell us where the 4 HP unit will sit and what power the site has, and you get a drawing and a price.
Get a free quote All refrigeration units
Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.