4 HP R-448A walk-in cooler refrigeration system
Updated
4 HP is for large walk-in coolers, well beyond our standard 10x12 package (1 1/2 HP): big custom boxes, long glass door runs, coolers outdoors in the sun. The heat load calculation sets the horsepower, then the power on site picks the series. This class has 8 current R-448A condensing units at 4 HP, rated 32,160 to 35,030 BTU/h at 95°F ambient, with the 6 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.
- Capacity. 33,300 to 36,200 BTU/h at 90°F ambient and 32,160 to 35,030 BTU/h at 95°F, about 2.7 to 2.9 tons of refrigeration.
- Next sizes. Smaller: 3-1/2 HP R-448A walk-in cooler system (29,760 BTU/h). Larger: 4-1/2 HP R-448A walk-in cooler system (39,190 BTU/h).
- Same horsepower in R-454A. 4 HP R-454A walk-in cooler system, 12 condensing units, 32,590 to 33,420 BTU/h at 95°F ambient.
4 HP R-448A condensing units
R-448A is the non-flammable A1 blend that replaces R-404A. Compare R-448A and R-454A.
| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
|---|---|---|---|---|---|---|---|---|
| WBOS04E4SEB | Next-Gen II Scroll | Indoor / Outdoor | Scroll · Non-Flooded | 33,300 | 32,160 | 208/230/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WBOS04E4SGB | Next-Gen II Scroll | Indoor / Outdoor | Scroll · Non-Flooded | 33,300 | 32,160 | 460/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WBO400E4SDB | Preassembled Remote | Indoor / Outdoor | Scroll | 36,200 | 35,030 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 352 lb |
| WBO400E4SEB | Preassembled Remote | Indoor / Outdoor | Scroll | 36,200 | 35,030 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 352 lb |
| WFOS04E4SEA | Next-Gen II Scroll | Outdoor | Scroll · Flooded | 33,300 | 32,160 | 208/230/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WFOS04E4SGA | Next-Gen II Scroll | Outdoor | Scroll · Flooded | 33,300 | 32,160 | 460/3/60 · 3-ph | 49 × 38-5/16 × 36-3/8″ | 700 lb |
| WFO400E4SDA | Preassembled Remote | Outdoor | Scroll | 36,200 | 35,030 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 352 lb |
| WFO400E4SEA | Preassembled Remote | Outdoor | Scroll | 36,200 | 35,030 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 352 lb |
Manufacturer ratings at 25°F suction.
Which 4 HP R-448A model fits your site
4 HP R-448A comes in two different series. The Preassembled Remote is rated higher, weighs about half as much and runs on 208-230 V single or three phase; the Next-Gen II Scroll sits in a larger, heavier cabinet and runs on three phase only, at 208/230 V or 460 V. A building with single phase power only needs the Preassembled Remote; a 460 V site needs the Next-Gen II Scroll.
- Next-Gen II Scroll, 4 models: cabinet 49 × 38 5/16 × 36 3/8 in., 700 lb; 33,300 BTU/h at 90°F and 32,160 BTU/h at 95°F; 208-230 V three phase and 460 V three phase.
- Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 352 lb; 36,200 BTU/h at 90°F and 35,030 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
- Indoors or outdoors. WBO400E4SDB on 208-230 V single phase; WBOS04E4SEB and WBO400E4SEB on 208-230 V three phase; WBOS04E4SGB on 460 V three phase.
- Outdoors only. WFO400E4SDA on 208-230 V single phase; WFOS04E4SEA and WFO400E4SEA on 208-230 V three phase; WFOS04E4SGA on 460 V three phase.
- Other refrigerant. The same 4 HP in R-454A (12 models, Next-Gen II and Next-Gen Mini-Con) is rated 32,590 to 33,420 BTU/h at 95°F, 5% less at the top of the range than R-448A, and weighs 352 to 700 lb. See the 4 HP R-454A walk-in cooler system.
Evaporators used with this system
A 4 HP R-448A condensing unit is matched to 6 medium-temperature unit coolers: 5 low profile and 1 ultra low profile center mount, rated 27,800 to 45,900 BTU/h.
| Model | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WE6A258ADAS | 30,400 | 3,150 | 5 | 112 × 28.375 × 13.75″ |
| Model | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WL6A235ADAS | 27,800 | 3,140 | 4 | 76.625 × 15.5 × 18.125″ |
| WL6A260ADAS | 30,400 | 3,100 | 4 | 76.625 × 15.5 × 18.125″ |
| WL6A295ADAS | 36,100 | 3,875 | 5 | 93.125 × 15.5 × 18.125″ |
| WL6A330ADAS | 38,800 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |
| WL6A390ADAS | 45,900 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |
Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.
4 HP R-448A cooler system questions
How many BTU is a 4 HP R-448A walk-in cooler system?
The 8 R-448A condensing units in this class are rated 33,300 to 36,200 BTU/h at 90°F ambient and 32,160 to 35,030 BTU/h at 95°F, about 2.7 to 2.9 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-454A the same horsepower is rated 32,590 to 33,420 BTU/h.
What size walk-in cooler does a 4 HP system fit?
4 HP is for large walk-in coolers, well beyond our standard 10x12 package (1 1/2 HP): big custom boxes, long glass door runs, coolers outdoors in the sun. The heat load calculation sets the horsepower, then the power on site picks the series.
Which 4 HP R-448A condensing unit goes indoors, and which outdoors?
Indoors or outdoors: WBO400E4SDB on 208-230 V single phase; WBOS04E4SEB and WBO400E4SEB on 208-230 V three phase; WBOS04E4SGB on 460 V three phase. Outdoors only: WFO400E4SDA on 208-230 V single phase; WFOS04E4SEA and WFO400E4SEA on 208-230 V three phase; WFOS04E4SGA on 460 V three phase.
Is the 4 HP R-448A unit single phase, three phase or 460 V?
208-230 V single phase: WBO400E4SDB and WFO400E4SDA. 208-230 V three phase: WBOS04E4SEB, WBO400E4SEB, WFOS04E4SEA and WFO400E4SEA. 460 V three phase: WBOS04E4SGB and WFOS04E4SGA.
How big and heavy is a 4 HP R-448A condensing unit?
Next-Gen II Scroll, 4 models: cabinet 49 × 38 5/16 × 36 3/8 in., 700 lb; 33,300 BTU/h at 90°F and 32,160 BTU/h at 95°F; 208-230 V three phase and 460 V three phase. Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 352 lb; 36,200 BTU/h at 90°F and 35,030 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
Need a 4 HP R-448A system sized for your walk-in cooler?
Send the inside dimensions and what it will store, tell us where the 4 HP unit will sit and what power the site has, and you get a drawing and a price.
Get a free quote All refrigeration units
Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.