4-1/2 HP R-448A walk-in cooler refrigeration system
Updated
4 1/2 HP goes on big walk-in coolers, three times the horsepower of our standard 10x12 (1 1/2 HP): large custom rooms, long glass door runs, coolers in full sun. It is picked at quote when the load sits near 39,000 BTU/h at 95°F. This class has 4 current R-448A condensing units at 4-1/2 HP, rated 39,190 BTU/h at 95°F ambient, with the 6 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.
- Capacity. 40,500 BTU/h at 90°F ambient and 39,190 BTU/h at 95°F, about 3.3 tons of refrigeration.
- Next sizes. Smaller: 4 HP R-448A walk-in cooler system (32,160 to 35,030 BTU/h). Larger: 5 HP R-448A walk-in cooler system (35,180 to 43,160 BTU/h).
- Same horsepower in R-454A. 4-1/2 HP R-454A walk-in cooler system, 8 condensing units, 37,170 BTU/h at 95°F ambient.
4-1/2 HP R-448A condensing units
R-448A is the non-flammable A1 blend that replaces R-404A. Compare R-448A and R-454A.
| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
|---|---|---|---|---|---|---|---|---|
| WBO450E4SDB | Preassembled Remote | Indoor / Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 375 lb |
| WBO450E4SEB | Preassembled Remote | Indoor / Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 375 lb |
| WFO450E4SDA | Preassembled Remote | Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 375 lb |
| WFO450E4SEA | Preassembled Remote | Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 375 lb |
Manufacturer ratings at 25°F suction.
Which 4 1/2 HP R-448A model fits your site
4 1/2 HP R-448A comes in one series, the Preassembled Remote: four models at 375 lb, rated 39,190 BTU/h at 95°F, about 3.3 tons, on 208-230 V single or three phase. That is more than the Next-Gen II Scroll units of the 4 HP (32,160) and the 5 HP (35,180), at about half their weight (700 and 710 lb). It has no 460 V model: a 460 V building takes the Next-Gen II Scroll at 4 or 5 HP, or the 4 1/2 HP R-454A.
- Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 375 lb; 40,500 BTU/h at 90°F and 39,190 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
- Indoors or outdoors. WBO450E4SDB on 208-230 V single phase; WBO450E4SEB on 208-230 V three phase.
- Outdoors only. WFO450E4SDA on 208-230 V single phase; WFO450E4SEA on 208-230 V three phase.
- Other refrigerant. The same 4 1/2 HP in R-454A (8 models, Next-Gen Mini-Con) is rated 37,170 BTU/h at 95°F, 5% less at the top of the range than R-448A, and weighs 375 lb. See the 4-1/2 HP R-454A walk-in cooler system.
Evaporators used with this system
A 4-1/2 HP R-448A condensing unit is matched to 6 medium-temperature unit coolers: 5 low profile and 1 ultra low profile center mount, rated 27,800 to 45,900 BTU/h.
| Model | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WE6A258ADAS | 30,400 | 3,150 | 5 | 112 × 28.375 × 13.75″ |
| Model | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WL6A235ADAS | 27,800 | 3,140 | 4 | 76.625 × 15.5 × 18.125″ |
| WL6A260ADAS | 30,400 | 3,100 | 4 | 76.625 × 15.5 × 18.125″ |
| WL6A295ADAS | 36,100 | 3,875 | 5 | 93.125 × 15.5 × 18.125″ |
| WL6A330ADAS | 38,800 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |
| WL6A390ADAS | 45,900 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |
Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.
4-1/2 HP R-448A cooler system questions
How many BTU is a 4 1/2 HP R-448A walk-in cooler system?
The 4 R-448A condensing units in this class are rated 40,500 BTU/h at 90°F ambient and 39,190 BTU/h at 95°F, about 3.3 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-454A the same horsepower is rated 37,170 BTU/h.
What size walk-in cooler does a 4 1/2 HP system fit?
4 1/2 HP goes on big walk-in coolers, three times the horsepower of our standard 10x12 (1 1/2 HP): large custom rooms, long glass door runs, coolers in full sun. It is picked at quote when the load sits near 39,000 BTU/h at 95°F.
Which 4 1/2 HP R-448A condensing unit goes indoors, and which outdoors?
Indoors or outdoors: WBO450E4SDB on 208-230 V single phase; WBO450E4SEB on 208-230 V three phase. Outdoors only: WFO450E4SDA on 208-230 V single phase; WFO450E4SEA on 208-230 V three phase.
Is the 4 1/2 HP R-448A unit single phase, three phase or 460 V?
208-230 V single phase: WBO450E4SDB and WFO450E4SDA. 208-230 V three phase: WBO450E4SEB and WFO450E4SEA. No model in this class runs on 460 V.
How big and heavy is a 4 1/2 HP R-448A condensing unit?
Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 375 lb; 40,500 BTU/h at 90°F and 39,190 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
Why is this 4 1/2 HP rated higher than a 5 HP Next-Gen II Scroll?
Horsepower is a nominal size and the two series are built differently, so compare BTU/h. The 4 1/2 HP Preassembled Remote is rated 39,190 BTU/h at 95°F; the 5 HP Next-Gen II Scroll is rated 35,180 and the 5 HP Preassembled Remote 43,160.
Need a 4 1/2 HP R-448A system sized for your walk-in cooler?
Send the inside dimensions and what it will store, tell us where the 4 1/2 HP unit will sit and what power the site has, and you get a drawing and a price.
Get a free quote All refrigeration units
Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.