FREE SHIPPING on every walk-in we quote  ·  Same-day quote
R-448A · Medium Temperature (Cooler)

3 HP R-448A walk-in cooler refrigeration system

Updated

In R-448A, 3 HP sits between 2 3/4 HP and 3 1/2 HP. It is chosen at quote when the calculated heat load of the cooler calls for about 28,000 BTU/h at 95°F: a large custom cooler, a cooler with a glass door wall or a cooler outdoors. This class has 4 current R-448A condensing units at 3 HP, rated 27,960 BTU/h at 95°F ambient, with the 7 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.

Outdoor remote refrigeration condensing unit of the type supplied with a 3 HP walk-in cooler system
3
Horsepower
27,960
BTU/h at 95°F ambient
4
Condensing units
7
Matched evaporators
4 models

3 HP R-448A condensing units

R-448A is the non-flammable A1 blend that replaces R-404A. Compare R-448A and R-454A.

3 HP R-448A Medium Temperature (Cooler) condensing units, 4 models
ModelSeriesSiting CompressorBTU/h @ 90°F BTU/h @ 95°FElectrical D × W × HWeight
WBO300E4SDB Preassembled Remote Indoor / Outdoor Scroll 28,900 27,960 208-230 · 1-ph 33 × 43.875 × 35″ 305 lb
WBO300E4SEB Preassembled Remote Indoor / Outdoor Scroll 28,900 27,960 208-230 · 3-ph 33 × 43.875 × 35″ 305 lb
WFO300E4SDA Preassembled Remote Outdoor Scroll 28,900 27,960 208-230 · 1-ph 33 × 43.875 × 35″ 305 lb
WFO300E4SEA Preassembled Remote Outdoor Scroll 28,900 27,960 208-230 · 3-ph 33 × 43.875 × 35″ 305 lb

Manufacturer ratings at 25°F suction.

Choosing the model

Which 3 HP R-448A model fits your site

3 HP R-448A is rated 27,960 BTU/h at 95°F, about 2.3 tons, a little more than the 27,380 of the 3 HP R-454A. The four R-448A models are Preassembled Remote units at 305 lb and run on 208-230 V single or three phase only; a building on 460 V takes the 3 HP R-454A, which has 460 V models.

  • Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 305 lb; 28,900 BTU/h at 90°F and 27,960 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
  • Indoors or outdoors. WBO300E4SDB on 208-230 V single phase; WBO300E4SEB on 208-230 V three phase.
  • Outdoors only. WFO300E4SDA on 208-230 V single phase; WFO300E4SEA on 208-230 V three phase.
  • Other refrigerant. The same 3 HP in R-454A (8 models, Next-Gen Mini-Con) is rated 27,380 BTU/h at 95°F, 2% less at the top of the range than R-448A, and weighs 305 lb. See the 3 HP R-454A walk-in cooler system.
7 unit coolers

Evaporators used with this system

A 3 HP R-448A condensing unit is matched to 7 medium-temperature unit coolers: 5 low profile and 2 ultra low profile center mount, rated 22,500 to 38,800 BTU/h.

Ultra low profile center mount, air defrost, 115 V: 2 models
ModelBTU/hCFMFansL × W × H
WE6A204ADAS 23,900 2,860 5 112 × 28.375 × 11.25″
WE6A258ADAS 30,400 3,150 5 112 × 28.375 × 13.75″
Low profile, air defrost, 115 V: 5 models
ModelBTU/hCFMFansL × W × H
WL6A195ADAS 22,500 3,140 4 76.625 × 15.5 × 18.125″
WL6A235ADAS 27,800 3,140 4 76.625 × 15.5 × 18.125″
WL6A260ADAS 30,400 3,100 4 76.625 × 15.5 × 18.125″
WL6A295ADAS 36,100 3,875 5 93.125 × 15.5 × 18.125″
WL6A330ADAS 38,800 4,650 6 109.625 × 15.5 × 18.125″

Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.

Straight answers

3 HP R-448A cooler system questions

How many BTU is a 3 HP R-448A walk-in cooler system?

The 4 R-448A condensing units in this class are rated 28,900 BTU/h at 90°F ambient and 27,960 BTU/h at 95°F, about 2.3 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-454A the same horsepower is rated 27,380 BTU/h.

What size walk-in cooler does a 3 HP system fit?

In R-448A, 3 HP sits between 2 3/4 HP and 3 1/2 HP. It is chosen at quote when the calculated heat load of the cooler calls for about 28,000 BTU/h at 95°F: a large custom cooler, a cooler with a glass door wall or a cooler outdoors.

Which 3 HP R-448A condensing unit goes indoors, and which outdoors?

Indoors or outdoors: WBO300E4SDB on 208-230 V single phase; WBO300E4SEB on 208-230 V three phase. Outdoors only: WFO300E4SDA on 208-230 V single phase; WFO300E4SEA on 208-230 V three phase.

Is the 3 HP R-448A unit single phase, three phase or 460 V?

208-230 V single phase: WBO300E4SDB and WFO300E4SDA. 208-230 V three phase: WBO300E4SEB and WFO300E4SEA. No model in this class runs on 460 V.

How big and heavy is a 3 HP R-448A condensing unit?

Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 305 lb; 28,900 BTU/h at 90°F and 27,960 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.

Need a 3 HP R-448A system sized for your walk-in cooler?

Send the inside dimensions and what it will store, tell us where the 3 HP unit will sit and what power the site has, and you get a drawing and a price.

Get a free quote All refrigeration units

Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.

← 2-3/4 HP R-448A cooler  ·  3 HP R-448A freezer →