3 HP R-454A walk-in cooler refrigeration system
Updated
3 HP is double the horsepower on our largest standard cooler (1 1/2 HP on a 10x12), so it goes on large custom coolers, glass door boxes with many doors and coolers taking in a lot of warm product. The heat load calculation sets it before anything is quoted. This class has 8 current R-454A condensing units at 3 HP, rated 27,380 BTU/h at 95°F ambient, with the 28 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.
- Capacity. 28,590 BTU/h at 90°F ambient and 27,380 BTU/h at 95°F, about 2.3 tons of refrigeration.
- Next sizes. Smaller: 2-3/4 HP R-454A walk-in cooler system (24,880 BTU/h). Larger: 3-1/2 HP R-454A walk-in cooler system (30,160 BTU/h).
- Same horsepower in R-448A. 3 HP R-448A walk-in cooler system, 4 condensing units, 27,960 BTU/h at 95°F ambient.
3 HP R-454A condensing units
R-454A is an A2L refrigerant: lower GWP, mildly flammable, installed to the manufacturer’s A2L requirements. Compare R-448A and R-454A.
| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
|---|---|---|---|---|---|---|---|---|
| WBON300E4ADA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 28,590 | 27,380 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WBON300E4AEA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 28,590 | 27,380 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WBON300E4AGA | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 28,590 | 27,380 | 460/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WFON300E4ADA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 28,590 | 27,380 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WFON300E4ADANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 28,590 | 27,380 | 208-230/1/60 · 1-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WFON300E4AEA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 28,590 | 27,380 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WFON300E4AEANT | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 28,590 | 27,380 | 208-230/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 305 lb |
| WFON300E4AGA | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 28,590 | 27,380 | 460/3/60 · 3-ph | 33 × 43-7/8 × 35″ | 305 lb |
Manufacturer ratings at 25°F suction.
Which 3 HP R-454A model fits your site
Every 3 HP R-454A model here is a Next-Gen Mini-Con in the same cabinet, about 2.3 tons of refrigeration at 95°F. It comes on all three services, 208-230 V single phase, 208-230 V three phase and 460 V three phase, so the building’s power rarely rules it out.
- Next-Gen Mini-Con, 8 models: cabinet 33 × 43 7/8 × 35 in., 305 lb; 28,590 BTU/h at 90°F and 27,380 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
- Indoors or outdoors. WBON300E4ADA on 208-230 V single phase; WBON300E4AEA on 208-230 V three phase; WBON300E4AGA on 460 V three phase.
- Outdoors only. WFON300E4ADA and WFON300E4ADANT on 208-230 V single phase; WFON300E4AEA and WFON300E4AEANT on 208-230 V three phase; WFON300E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
- Other refrigerant. The same 3 HP in R-448A (4 models, Preassembled Remote) is rated 27,960 BTU/h at 95°F, 2% more at the top of the range than R-454A, and weighs 305 lb. See the 3 HP R-448A walk-in cooler system.
Evaporators used with this system
A 3 HP R-454A condensing unit is matched to 28 medium-temperature unit coolers: 14 medium profile, 10 low profile and 4 center mount, rated 22,000 to 37,500 BTU/h.
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAE6A249ADA 115/1/60 WAE6A249DDA 208-230/1/60 |
24,900 | 2,860 | 5 | 116 × 28-3/8 × 11-1/4″ |
| WAE6A316ADA 115/1/60 WAE6A316DDA 208-230/1/60 |
31,600 | 3,150 | 5 | 116 × 28-3/8 × 13-3/4″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAL6A220ADA 115/1/60 WAL6A220DDA 208-230/1/60 |
22,000 | 2,325 | 3 | 60-1/8 × 15-1/2 × 18-1/8″ |
| WAL6A234ADA 115/1/60 WAL6A234DDA 208-230/1/60 |
23,400 | 3,140 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A289ADA 115/1/60 WAL6A289DDA 208-230/1/60 |
28,900 | 3,140 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A316ADA 115/1/60 WAL6A316DDA 208-230/1/60 |
31,600 | 3,199 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |
| WAL6A375ADA 115/1/60 WAL6A375DDA 208-230/1/60 |
37,500 | 3,875 | 5 | 93-1/8 × 15-1/2 × 18-1/8″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAM6A268ADA 115/1/60 WAM6A268DDA 208-230/1/60 WAM6A268FDA 460/1/60 |
26,800 | 2,950 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |
| WAM6A336ADA 115/1/60 WAM6A336DDA 208-230/1/60 WAM6A336FDA 460/1/60 |
33,600 | 6,950 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
| Model and voltage | BTU/h | CFM | Fans | L × W × H |
|---|---|---|---|---|
| WAM6D267DDA 208-230/1/60 WAM6D267EDA 208-230/3/60 WAM6D267FDA 460/1/60 WAM6D267GDA 460/3/60 |
26,800 | 2,950 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |
| WAM6D335DDA 208-230/1/60 WAM6D335EDA 208-230/3/60 WAM6D335FDA 460/1/60 WAM6D335GDA 460/3/60 |
33,600 | 6,950 | 2 | 80-1/2 × 21-5/16 × 33-7/8″ |
Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.
3 HP R-454A cooler system questions
How many BTU is a 3 HP R-454A walk-in cooler system?
The 8 R-454A condensing units in this class are rated 28,590 BTU/h at 90°F ambient and 27,380 BTU/h at 95°F, about 2.3 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-448A the same horsepower is rated 27,960 BTU/h.
What size walk-in cooler does a 3 HP system fit?
3 HP is double the horsepower on our largest standard cooler (1 1/2 HP on a 10x12), so it goes on large custom coolers, glass door boxes with many doors and coolers taking in a lot of warm product. The heat load calculation sets it before anything is quoted.
Which 3 HP R-454A condensing unit goes indoors, and which outdoors?
Indoors or outdoors: WBON300E4ADA on 208-230 V single phase; WBON300E4AEA on 208-230 V three phase; WBON300E4AGA on 460 V three phase. Outdoors only: WFON300E4ADA and WFON300E4ADANT on 208-230 V single phase; WFON300E4AEA and WFON300E4AEANT on 208-230 V three phase; WFON300E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
Is the 3 HP R-454A unit single phase, three phase or 460 V?
208-230 V single phase: WBON300E4ADA, WFON300E4ADA and WFON300E4ADANT. 208-230 V three phase: WBON300E4AEA, WFON300E4AEA and WFON300E4AEANT. 460 V three phase: WBON300E4AGA and WFON300E4AGA.
How big and heavy is a 3 HP R-454A condensing unit?
Next-Gen Mini-Con, 8 models: cabinet 33 × 43 7/8 × 35 in., 305 lb; 28,590 BTU/h at 90°F and 27,380 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
Which unit coolers are on the 3 HP list but not the 3 1/2 HP list?
WAL6A220 and WAL6A234, each at 115 V and 208-230 V. The 3 1/2 HP lists the larger WAL6A404 in their place, and the other 24 coils serve both sizes.
What is the largest unit cooler for a 3 HP R-454A system?
The low profile WAL6A375, rated 37,500 BTU/h with 3,875 CFM on five fans. It is also the one coil here that the 2 3/4 HP class does not list.
What medium profile coils can a 3 HP R-454A system use?
Two sizes. One is rated 26,800 BTU/h with 2,950 CFM on one fan (WAM6A268 with air defrost, WAM6D267 with electric defrost). The other is rated 33,600 BTU/h with 6,950 CFM on two fans (WAM6A336 and WAM6D335). The air defrost versions run on 115 V, 208-230 V or 460 V single phase; the electric defrost versions on 208-230 V or 460 V, single or three phase.
Need a 3 HP R-454A system sized for your walk-in cooler?
Send the inside dimensions and what it will store, tell us where the 3 HP unit will sit and what power the site has, and you get a drawing and a price.
Get a free quote All refrigeration units
Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.