FREE SHIPPING on every walk-in we quote  ·  Same-day quote
R-448A · Low Temperature (Freezer)

5 HP R-448A walk-in freezer refrigeration system

Updated

5 HP is above our standard freezer packages, the largest of which carries 2 1/2 HP on an 8x10 or 10x10. We choose it at quote when the heat load calls for about 16,100 BTU/h at 95°F: a custom size, glass doors or an outdoor location. This class has 4 current R-448A condensing units at 5 HP, rated 16,070 BTU/h at 95°F ambient, with the 8 unit coolers matched to that capacity, for a walk-in freezer holding 0°F to -10°F.

Outdoor remote refrigeration condensing unit of the type supplied with a 5 HP walk-in freezer system
5
Horsepower
16,070
BTU/h at 95°F ambient
4
Condensing units
8
Matched evaporators
4 models

5 HP R-448A condensing units

R-448A is the non-flammable A1 blend that replaces R-404A. Compare R-448A and R-454A.

5 HP R-448A Low Temperature (Freezer) condensing units, 4 models
ModelSeriesSiting CompressorBTU/h @ 90°F BTU/h @ 95°FElectrical D × W × HWeight
WBO500L4SDB Preassembled Remote Indoor / Outdoor Scroll 16,700 16,070 208-230 · 1-ph 33 × 43.875 × 35″ 367 lb
WBO500L4SEB Preassembled Remote Indoor / Outdoor Scroll 16,700 16,070 208-230 · 3-ph 33 × 43.875 × 35″ 367 lb
WFO500L4SDB Preassembled Remote Outdoor Scroll 16,700 16,070 208-230 · 1-ph 33 × 43.875 × 35″ 367 lb
WFO500L4SEB Preassembled Remote Outdoor Scroll 16,700 16,070 208-230 · 3-ph 33 × 43.875 × 35″ 367 lb

Manufacturer ratings at -20°F suction.

Choosing the model

Which 5 HP R-448A model fits your site

5 HP R-448A is rated up to 16,070 BTU/h at 95°F (about 1.3 tons) at -20°F suction, from 4 Preassembled Remote models. Compared with the 4 HP below it: 3,080 BTU/h more (24%), the same cabinet, 367 lb against 352 lb. Of its 8 matched unit coolers, 5 also serve the 4 HP. The 6 HP above it is rated 19,440 BTU/h: the same cabinet, 383 lb against 367 lb here.

  • Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 367 lb; 16,700 BTU/h at 90°F and 16,070 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
  • Indoors or outdoors. WBO500L4SDB on 208-230 V single phase; WBO500L4SEB on 208-230 V three phase.
  • Outdoors only. WFO500L4SDB on 208-230 V single phase; WFO500L4SEB on 208-230 V three phase.
  • Other refrigerant. The same 5 HP in R-454A (8 models, Next-Gen Mini-Con) is rated 17,770 BTU/h at 95°F, 11% more at the top of the range than R-448A, and weighs 367 lb. See the 5 HP R-454A walk-in freezer system.
8 unit coolers

Evaporators used with this system

A 5 HP R-448A condensing unit is matched to 8 low-temperature unit coolers: 4 low profile, 3 ultra low profile center mount and 1 slim display case, rated 14,200 to 21,000 BTU/h.

Ultra low profile center mount, electric defrost, 208-230 V: 3 models
ModelBTU/hCFMFansL × W × H
WE6E125DDS 14,300 1,716 3 72 × 28.375 × 11.25″
WE6E137DDS 15,400 2,408 4 92 × 28.375 × 11.25″
WE6E182DDS 20,900 2,288 4 92 × 28.375 × 11.25″
Low profile, electric defrost, 208-230 V: 4 models
ModelBTU/hCFMFansL × W × H
WL6E121DDAS 14,200 2,355 3 60.125 × 15.5 × 18.125″
WL6E142DDAS 16,600 2,325 3 60.125 × 15.5 × 18.125″
WL6E162DDAS 18,700 3,140 4 76.625 × 15.5 × 18.125″
WL6E182DDAS 21,000 3,100 4 76.625 × 15.5 × 18.125″
Slim display case, electric defrost, 208-230 V: 1 model
ModelBTU/hCFMFansL × W × H
ASLE65150DDS 16,200 2,850 6 139 × 19.8125 × 9.1875″

Coil ratings use their own, smaller temperature difference, so they read higher than the condensing unit and do not compare one for one. Questions: 954-237-6753.

Straight answers

5 HP R-448A freezer system questions

How many BTU is a 5 HP R-448A walk-in freezer system?

The 4 R-448A condensing units in this class are rated 16,700 BTU/h at 90°F ambient and 16,070 BTU/h at 95°F, about 1.3 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at -20°F suction). In R-454A the same horsepower is rated 17,770 BTU/h.

What size walk-in freezer does a 5 HP system fit?

5 HP is above our standard freezer packages, the largest of which carries 2 1/2 HP on an 8x10 or 10x10. We choose it at quote when the heat load calls for about 16,100 BTU/h at 95°F: a custom size, glass doors or an outdoor location. We do the heat load calculation before anything is quoted.

Which 5 HP R-448A condensing unit goes indoors, and which outdoors?

Indoors or outdoors: WBO500L4SDB on 208-230 V single phase; WBO500L4SEB on 208-230 V three phase. Outdoors only: WFO500L4SDB on 208-230 V single phase; WFO500L4SEB on 208-230 V three phase.

Is the 5 HP R-448A unit single phase, three phase or 460 V?

208-230 V single phase: WBO500L4SDB and WFO500L4SDB. 208-230 V three phase: WBO500L4SEB and WFO500L4SEB. No model in this class runs on 460 V.

How big and heavy is a 5 HP R-448A condensing unit?

Preassembled Remote, 4 models: cabinet 33 × 43 7/8 × 35 in., 367 lb; 16,700 BTU/h at 90°F and 16,070 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.

Need a 5 HP R-448A system sized for your walk-in freezer?

Send the inside dimensions and what it will store, tell us where the 5 HP unit will sit and what power the site has, and you get a drawing and a price.

Get a free quote All refrigeration units

Condensing units UL and cUL listed; unit coolers also NSF approved and AWEF certified. Listing details.

← 5 HP R-448A cooler  ·  6 HP R-448A cooler →