title: "4-1/2 HP R-448A Walk-In Cooler Refrigeration System | Frigid Coolers LLC"
description: "4-1/2 HP R-448A walk-in cooler system, sized at quote from your heat load: 39,190 BTU/h at 95°F, 4 condensing units, 6 matched evaporators."
url: "https://www.frigidcoolers.com/refrigeration/4-1-2-hp-r-448a-walk-in-cooler-refrigeration-system"
language: "en"
published: "2026-10-07"
updated: "2026-11-21T23:36:46+00:00"
---

# 4-1/2 HP R-448A walk-in cooler refrigeration system

Updated November 21, 2026

4 1/2 HP goes on big walk-in coolers, three times the horsepower of our standard 10x12 (1 1/2 HP): large custom rooms, long glass door runs, coolers in full sun. It is picked at quote when the load sits near 39,000 BTU/h at 95°F. This class has 4 current R-448A condensing units at 4-1/2 HP, rated 39,190 BTU/h at 95°F ambient, with the 6 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.

- **Capacity.** 40,500 BTU/h at 90°F ambient and 39,190 BTU/h at 95°F, about 3.3 tons of refrigeration.
- **Next sizes.** Smaller: [4 HP R-448A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/4-hp-r-448a-walk-in-cooler-refrigeration-system) (32,160 to 35,030 BTU/h). Larger: [5 HP R-448A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/5-hp-r-448a-walk-in-cooler-refrigeration-system) (35,180 to 43,160 BTU/h).
- **Same horsepower in R-454A.** [4-1/2 HP R-454A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/4-1-2-hp-r-454a-walk-in-cooler-refrigeration-system), 8 condensing units, 37,170 BTU/h at 95°F ambient.

- **4-1/2** Horsepower
- **39,190** BTU/h at 95°F ambient
- **4** Condensing units
- **6** Matched evaporators

## 4-1/2 HP R-448A condensing units

R-448A is the non-flammable A1 blend that replaces R-404A. [Compare R-448A and R-454A](https://www.frigidcoolers.com/galleries/equipment#faq).

*4-1/2 HP R-448A Medium Temperature (Cooler) condensing units, 4 models*

| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| **WBO450E4SDB** | Preassembled Remote | Indoor / Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 375 lb |
| **WBO450E4SEB** | Preassembled Remote | Indoor / Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 375 lb |
| **WFO450E4SDA** | Preassembled Remote | Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 1-ph | 33 × 43.875 × 35″ | 375 lb |
| **WFO450E4SEA** | Preassembled Remote | Outdoor | Scroll | 40,500 | 39,190 | 208-230 · 3-ph | 33 × 43.875 × 35″ | 375 lb |

Manufacturer ratings at 25°F suction.

## Which 4 1/2 HP R-448A model fits your site

4 1/2 HP R-448A comes in one series, the Preassembled Remote: four models at 375 lb, rated 39,190 BTU/h at 95°F, about 3.3 tons, on 208-230 V single or three phase. That is more than the Next-Gen II Scroll units of the 4 HP (32,160) and the 5 HP (35,180), at about half their weight (700 and 710 lb). It has no 460 V model: a 460 V building takes the Next-Gen II Scroll at 4 or 5 HP, or the 4 1/2 HP R-454A.

- **Preassembled Remote**, 4 models: cabinet 33 × 43 7/8 × 35 in., 375 lb; 40,500 BTU/h at 90°F and 39,190 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.
- **Indoors or outdoors.** WBO450E4SDB on 208-230 V single phase; WBO450E4SEB on 208-230 V three phase.
- **Outdoors only.** WFO450E4SDA on 208-230 V single phase; WFO450E4SEA on 208-230 V three phase.
- **Other refrigerant.** The same 4 1/2 HP in R-454A (8 models, Next-Gen Mini-Con) is rated 37,170 BTU/h at 95°F, 5% less at the top of the range than R-448A, and weighs 375 lb. See the [4-1/2 HP R-454A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/4-1-2-hp-r-454a-walk-in-cooler-refrigeration-system).

## Evaporators used with this system

A 4-1/2 HP R-448A condensing unit is matched to 6 medium-temperature unit coolers: 5 low profile and 1 ultra low profile center mount, rated 27,800 to 45,900 BTU/h.

*Ultra low profile center mount, air defrost, 115 V: 1 model*

| Model | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WE6A258ADAS** | 30,400 | 3,150 | 5 | 112 × 28.375 × 13.75″ |

*Low profile, air defrost, 115 V: 5 models*

| Model | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WL6A235ADAS** | 27,800 | 3,140 | 4 | 76.625 × 15.5 × 18.125″ |
| **WL6A260ADAS** | 30,400 | 3,100 | 4 | 76.625 × 15.5 × 18.125″ |
| **WL6A295ADAS** | 36,100 | 3,875 | 5 | 93.125 × 15.5 × 18.125″ |
| **WL6A330ADAS** | 38,800 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |
| **WL6A390ADAS** | 45,900 | 4,650 | 6 | 109.625 × 15.5 × 18.125″ |

Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.

## 4-1/2 HP R-448A cooler system questions

### How many BTU is a 4 1/2 HP R-448A walk-in cooler system?

The 4 R-448A condensing units in this class are rated 40,500 BTU/h at 90°F ambient and 39,190 BTU/h at 95°F, about 3.3 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-454A the same horsepower is rated 37,170 BTU/h.

### What size walk-in cooler does a 4 1/2 HP system fit?

4 1/2 HP goes on big walk-in coolers, three times the horsepower of our standard 10x12 (1 1/2 HP): large custom rooms, long glass door runs, coolers in full sun. It is picked at quote when the load sits near 39,000 BTU/h at 95°F.

### Which 4 1/2 HP R-448A condensing unit goes indoors, and which outdoors?

Indoors or outdoors: WBO450E4SDB on 208-230 V single phase; WBO450E4SEB on 208-230 V three phase. Outdoors only: WFO450E4SDA on 208-230 V single phase; WFO450E4SEA on 208-230 V three phase.

### Is the 4 1/2 HP R-448A unit single phase, three phase or 460 V?

208-230 V single phase: WBO450E4SDB and WFO450E4SDA. 208-230 V three phase: WBO450E4SEB and WFO450E4SEA. No model in this class runs on 460 V.

### How big and heavy is a 4 1/2 HP R-448A condensing unit?

**Preassembled Remote**, 4 models: cabinet 33 × 43 7/8 × 35 in., 375 lb; 40,500 BTU/h at 90°F and 39,190 BTU/h at 95°F; 208-230 V single phase and 208-230 V three phase.

### Why is this 4 1/2 HP rated higher than a 5 HP Next-Gen II Scroll?

Horsepower is a nominal size and the two series are built differently, so compare BTU/h. The 4 1/2 HP Preassembled Remote is rated 39,190 BTU/h at 95°F; the 5 HP Next-Gen II Scroll is rated 35,180 and the 5 HP Preassembled Remote 43,160.

## Need a 4 1/2 HP R-448A system sized for your walk-in cooler?

Send the inside dimensions and what it will store, tell us where the 4 1/2 HP unit will sit and what power the site has, and you get a drawing and a price.

Condensing units **UL and cUL listed**; unit coolers also **NSF approved** and AWEF certified. [Listing details](https://www.frigidcoolers.com/galleries/equipment).

[← 4 HP R-448A freezer](https://www.frigidcoolers.com/refrigeration/4-hp-r-448a-walk-in-freezer-refrigeration-system) · [5 HP R-448A cooler →](https://www.frigidcoolers.com/refrigeration/5-hp-r-448a-walk-in-cooler-refrigeration-system)

---

Frigid Coolers LLC, Miami, Florida. Phone 954-237-6753 (call, or text pictures), sales@frigidcoolers.com. Quote form: https://www.frigidcoolers.com/#quote. This file is the Markdown copy of https://www.frigidcoolers.com/refrigeration/4-1-2-hp-r-448a-walk-in-cooler-refrigeration-system. Site map for AI assistants: https://www.frigidcoolers.com/llms.txt