# 2-1/2 HP R-454A walk-in cooler refrigeration system

Updated November 22, 2026

2 1/2 HP is chosen at quote when the heat load of a walk-in cooler calls for about 18,500 BTU/h at 95°F, more than the 1 1/2 HP of our standard 10x12 delivers: a bigger custom cooler, a glass door box or a cooler outdoors. This class has 8 current R-454A condensing units at 2-1/2 HP, rated 18,490 BTU/h at 95°F ambient, with the 25 unit coolers matched to that capacity, for a walk-in cooler holding 35°F.

- **Capacity.** 19,360 BTU/h at 90°F ambient and 18,490 BTU/h at 95°F, about 1.5 tons of refrigeration.
- **Next sizes.** Smaller: [2 HP R-454A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/2-hp-r-454a-walk-in-cooler-refrigeration-system) (16,890 BTU/h). Larger: [2-3/4 HP R-454A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/2-3-4-hp-r-454a-walk-in-cooler-refrigeration-system) (24,880 BTU/h).
- **Same horsepower in R-448A.** [2-1/2 HP R-448A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/2-1-2-hp-r-448a-walk-in-cooler-refrigeration-system), 4 condensing units, 18,770 BTU/h at 95°F ambient.

- **2-1/2** Horsepower
- **18,490** BTU/h at 95°F ambient
- **8** Condensing units
- **25** Matched evaporators

## 2-1/2 HP R-454A condensing units

R-454A is an A2L refrigerant: lower GWP, mildly flammable, installed to the manufacturer’s A2L requirements. [Compare R-448A and R-454A](https://www.frigidcoolers.com/galleries/equipment#faq).

*2-1/2 HP R-454A Medium Temperature (Cooler) condensing units, 8 models*

| Model | Series | Siting | Compressor | BTU/h @ 90°F | BTU/h @ 95°F | Electrical | D × W × H | Weight |
| --- | --- | --- | --- | --- | --- | --- | --- | --- |
| **WBON250E4ADA** | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 19,360 | 18,490 | 208-230/1/60 · 1-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WBON250E4AEA** | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 19,360 | 18,490 | 208-230/3/60 · 3-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WBON250E4AGA** | Next-Gen Mini-Con | Indoor / Outdoor | Scroll · Non-Flooded | 19,360 | 18,490 | 460/3/60 · 3-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WFON250E4ADA** | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 19,360 | 18,490 | 208-230/1/60 · 1-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WFON250E4ADANT** | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 19,360 | 18,490 | 208-230/1/60 · 1-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WFON250E4AEA** | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 19,360 | 18,490 | 208-230/3/60 · 3-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WFON250E4AEANT** | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 19,360 | 18,490 | 208-230/3/60 · 3-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |
| **WFON250E4AGA** | Next-Gen Mini-Con | Outdoor | Scroll · Flooded | 19,360 | 18,490 | 460/3/60 · 3-ph | 28-1/4 × 39-7/8 × 21-1/4″ | 230 lb |

Manufacturer ratings at 25°F suction.

## Which 2 1/2 HP R-454A model fits your site

2 1/2 HP R-454A is rated 18,490 BTU/h at 95°F, about 1.5 tons, from eight Next-Gen Mini-Con models at 230 lb. Unlike the 2 1/2 HP R-448A, it includes 460 V three phase models, and it is matched to a wider choice of unit coolers: 25, including 7 medium profile coils.

- **Next-Gen Mini-Con**, 8 models: cabinet 28 1/4 × 39 7/8 × 21 1/4 in., 230 lb; 19,360 BTU/h at 90°F and 18,490 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.
- **Indoors or outdoors.** WBON250E4ADA on 208-230 V single phase; WBON250E4AEA on 208-230 V three phase; WBON250E4AGA on 460 V three phase.
- **Outdoors only.** WFON250E4ADA and WFON250E4ADANT on 208-230 V single phase; WFON250E4AEA and WFON250E4AEANT on 208-230 V three phase; WFON250E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.
- **Other refrigerant.** The same 2 1/2 HP in R-448A (4 models, Preassembled Remote) is rated 18,770 BTU/h at 95°F, 2% more at the top of the range than R-454A, and weighs 230 lb. See the [2-1/2 HP R-448A walk-in cooler system](https://www.frigidcoolers.com/refrigeration/2-1-2-hp-r-448a-walk-in-cooler-refrigeration-system).

## Evaporators used with this system

A 2-1/2 HP R-454A condensing unit is matched to 25 medium-temperature unit coolers: 10 low profile, 8 center mount and 7 medium profile, rated 15,700 to 24,900 BTU/h.

*Center mount, air defrost: 8 models*

| Model and voltage | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WAE6A157ADA** 115/1/60 **WAE6A157DDA** 208-230/1/60 | 15,700 | 1,716 | 3 | 76 × 28-3/8 × 11-1/4″ |
| **WAE6A173ADA** 115/1/60 **WAE6A173DDA** 208-230/1/60 | 17,300 | 2,408 | 4 | 96 × 28-3/8 × 11-1/4″ |
| **WAE6A207ADA** 115/1/60 **WAE6A207DDA** 208-230/1/60 | 20,700 | 2,288 | 4 | 96 × 28-3/8 × 11-1/4″ |
| **WAE6A249ADA** 115/1/60 **WAE6A249DDA** 208-230/1/60 | 24,900 | 2,860 | 5 | 116 × 28-3/8 × 11-1/4″ |

*Low profile, air defrost: 10 models*

| Model and voltage | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WAL6A159ADA** 115/1/60 **WAL6A159DDA** 208-230/1/60 | 15,900 | 1,550 | 2 | 43-5/8 × 15-1/2 × 18-1/8″ |
| **WAL6A170ADA** 115/1/60 **WAL6A170DDA** 208-230/1/60 | 17,000 | 2,355 | 3 | 60-1/8 × 15-1/2 × 18-1/8″ |
| **WAL6A196ADA** 115/1/60 **WAL6A196DDA** 208-230/1/60 | 19,600 | 2,355 | 3 | 60-1/8 × 15-1/2 × 18-1/8″ |
| **WAL6A220ADA** 115/1/60 **WAL6A220DDA** 208-230/1/60 | 22,000 | 2,325 | 3 | 60-1/8 × 15-1/2 × 18-1/8″ |
| **WAL6A234ADA** 115/1/60 **WAL6A234DDA** 208-230/1/60 | 23,400 | 3,140 | 4 | 76-5/8 × 15-1/2 × 18-1/8″ |

*Medium profile, air defrost: 3 models*

| Model and voltage | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WAM6A219ADA** 115/1/60 **WAM6A219DDA** 208-230/1/60 **WAM6A219FDA** 460/1/60 | 21,900 | 3,190 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |

*Medium profile, electric defrost: 4 models*

| Model and voltage | BTU/h | CFM | Fans | L × W × H |
| --- | --- | --- | --- | --- |
| **WAM6D218DDA** 208-230/1/60 **WAM6D218EDA** 208-230/3/60 **WAM6D218FDA** 460/1/60 **WAM6D218GDA** 460/3/60 | 21,900 | 3,190 | 1 | 47-1/2 × 21-5/16 × 33-7/8″ |

Coil ratings use their own temperature difference and do not compare one for one with the condensing unit. Questions: 954-237-6753.

## 2-1/2 HP R-454A cooler system questions

### How many BTU is a 2 1/2 HP R-454A walk-in cooler system?

The 8 R-454A condensing units in this class are rated 19,360 BTU/h at 90°F ambient and 18,490 BTU/h at 95°F, about 1.5 tons of refrigeration (one ton is 12,000 BTU/h; manufacturer ratings at 25°F suction). In R-448A the same horsepower is rated 18,770 BTU/h.

### What size walk-in cooler does a 2 1/2 HP system fit?

2 1/2 HP is chosen at quote when the heat load of a walk-in cooler calls for about 18,500 BTU/h at 95°F, more than the 1 1/2 HP of our standard 10x12 delivers: a bigger custom cooler, a glass door box or a cooler outdoors.

### Which 2 1/2 HP R-454A condensing unit goes indoors, and which outdoors?

Indoors or outdoors: WBON250E4ADA on 208-230 V single phase; WBON250E4AEA on 208-230 V three phase; WBON250E4AGA on 460 V three phase. Outdoors only: WFON250E4ADA and WFON250E4ADANT on 208-230 V single phase; WFON250E4AEA and WFON250E4AEANT on 208-230 V three phase; WFON250E4AGA on 460 V three phase. The outdoor-only models are listed with a flooded condenser, for head pressure control in cold weather.

### Is the 2 1/2 HP R-454A unit single phase, three phase or 460 V?

208-230 V single phase: WBON250E4ADA, WFON250E4ADA and WFON250E4ADANT. 208-230 V three phase: WBON250E4AEA, WFON250E4AEA and WFON250E4AEANT. 460 V three phase: WBON250E4AGA and WFON250E4AGA.

### How big and heavy is a 2 1/2 HP R-454A condensing unit?

**Next-Gen Mini-Con**, 8 models: cabinet 28 1/4 × 39 7/8 × 21 1/4 in., 230 lb; 19,360 BTU/h at 90°F and 18,490 BTU/h at 95°F; 208-230 V single phase, 208-230 V three phase and 460 V three phase.

### How big is the jump from 2 1/2 HP to 2 3/4 HP in R-454A?

Large: 18,490 to 24,880 BTU/h at 95°F, a gain of 6,390 or about 35%. The machine grows with it, from 28 1/4 × 39 7/8 × 21 1/4 in. at 230 lb to 33 × 43 7/8 × 35 in. at 305 lb. Of the 25 coils listed here, 15 carry over to the larger size.

### What is the largest unit cooler matched to a 2 1/2 HP R-454A system?

By rating, the center mount WAE6A249: 24,900 BTU/h, 2,860 CFM and five fans, as WAE6A249ADA on 115 V or WAE6A249DDA on 208-230 V. The 2 HP class does not list it. Next comes the low profile WAL6A234 at 23,400 BTU/h, which moves more air, 3,140 CFM, with four fans. At the small end, center mount coils start at 15,700 BTU/h and low profile coils at 15,900.

### Is the 2 1/2 HP R-454A unit the same size as the R-448A one?

Yes, both measure 28 1/4 × 39 7/8 × 21 1/4 in. and weigh 230 lb. The R-448A is rated 18,770 BTU/h at 95°F, 280 more, or about 1.5%. The refrigerants do not share a unit cooler, so a coil chosen for one does not carry over to the other.

### Which 2 1/2 HP R-454A unit coolers run on 460 V?

Only medium profile coils: WAM6A219FDA with air defrost on 460 V single phase, and WAM6D218FDA and WAM6D218GDA with electric defrost on 460 V single and three phase. Every center mount and low profile coil in this class is 115 V or 208-230 V single phase, so a 460 V building that wants one of those needs a lower voltage supply for the coil.

## Need a 2 1/2 HP R-454A system sized for your walk-in cooler?

Send the inside dimensions and what it will store, tell us where the 2 1/2 HP unit will sit and what power the site has, and you get a drawing and a price.

Condensing units **UL and cUL listed**; unit coolers also **NSF approved** and AWEF certified. [Listing details](https://www.frigidcoolers.com/galleries/equipment).

[← 2-1/3 HP R-454A freezer](https://www.frigidcoolers.com/refrigeration/2-1-3-hp-r-454a-walk-in-freezer-refrigeration-system) · [2-1/2 HP R-454A freezer →](https://www.frigidcoolers.com/refrigeration/2-1-2-hp-r-454a-walk-in-freezer-refrigeration-system)

---

Frigid Coolers LLC, Miami, Florida. Phone 954-237-6753 (call, or text pictures), sales@frigidcoolers.com. Quote form: https://www.frigidcoolers.com/#quote. This file is the Markdown copy of https://www.frigidcoolers.com/refrigeration/2-1-2-hp-r-454a-walk-in-cooler-refrigeration-system. Site map for AI assistants: https://www.frigidcoolers.com/llms.txt